dc.description.abstractA case study has been carried out to investigate how process data from Frognerparken Pumping Station can be used more efficiently to get an early detection of degradation or failures of the pump systems. The technical condition is described by use of a single number from 0 to 100, denoted as the Technical Condition Index (TCI), where maximum value describes the design condition as new and the minimum value describes the state of total degradation. As presented in this paper, the pump station is broken down to subsystems where each subsystem consists of several nodes with its own TCI value. The overall pump station's TCI number is then computed by aggregating a weighted sum of all the subsystems’ TCIs. A method for early failure detection is also developed and is based on combining energy balance law together with the nonlinear extended Kalman filter to estimate model parameters for both the heating and the cooling phase of the pump. The model parameters are directly related to the temperature change and will give an indication of degradation during the transient phase even if the pump is working properly. During a visual inspection one of the pump had significantly higher temperature and vibration compared to the other pumps, and based on received timeseries for that specific day, we were able to validate the proposed method with realistic data.nb_NO
dc.language.isoengnb_NO
dc.publisherElsevier Ltd.nb_NO
dc.rightsAttribution-NonCommercial-NoDerivatives 4.0 Internasjonal*
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/deed.no*
dc.subjectCondition monitoringnb_NO
dc.subjectFault-diagnosisnb_NO
dc.subjectTechnical condition indexnb_NO
dc.subjectExtended Kalman filteringnb_NO
dc.subjectCase studynb_NO
dc.titleCondition monitoring for early failure detection. Frognerparken pumping station as case studynb_NO
dc.title.alternative12th International Conference on Computing and Control for the Water Industry, CCWI2013nb_NO
dc.typeJournal articlenb_NO
dc.typePeer reviewednb_NO
dc.description.versionpublishedVersionnb_NO
dc.rights.holder© The Authors. This is an open access article under the CC BY-NC-ND licensenb_NO
dc.subject.nsiVDP::Technology: 500nb_NO
dc.source.pagenumber162-171nb_NO
dc.source.volume70nb_NO
dc.source.journalProcedia Engineeringnb_NO
dc.identifier.doi10.1016/j.proeng.2014.02.019
dc.identifier.cristin1130638
cristin.unitcode7401,90,23,0
cristin.unitcode7401,30,30,0
cristin.unitnameAnvendt kybernetikk
cristin.unitnameInfrastruktur
cristin.ispublishedtrue
cristin.fulltextoriginal
cristin.qualitycode1


Tilhørende fil(er)

Thumbnail

Denne innførselen finnes i følgende samling(er)

Vis enkel innførsel

Attribution-NonCommercial-NoDerivatives 4.0 Internasjonal
Med mindre annet er angitt, så er denne innførselen lisensiert som Attribution-NonCommercial-NoDerivatives 4.0 Internasjonal