dc.description.abstractTwo fire experiments have been conducted to study sprinkler system extinguishing performance in a compartment (13 m2) with an adjacent corridor (12 m2), both with exposed cross-laminated timber (CLT). Four nozzles were installed in the corridor and two in the compartment. In Experiment 1, the sprinkler system was fully functional and successfully controlled a concealed fire. In Experiment 2, nozzles in the compartment were disconnected, while the corridor nozzles were operative, giving flashover after 5 min with large flames emerging into the corridor, rapidly worsening evacuation conditions. Despite four activated nozzles in the corridor, the temperatures remained high, and flames spread through the corridor along the CLT ceiling and the upper parts of the wall, an area that was not effectively protected by the nozzles. After flashover, the compartment temperatures remained stable at ∼1000 °C until experiment termination at 96 min. This continued fire in the compartment can be explained by water from the corridor sprinklers not reaching this area, extensive radiative feedback by the CLT surfaces and delamination of CLT elements of the 20 mm layers. The charring rate was ≥1.1 mm/min for large parts of the exposed CLT wall and ceiling in the compartment during the fire.en_US
dc.language.isoengen_US
dc.publisherElsevieren_US
dc.rightsNavngivelse 4.0 Internasjonal*
dc.rights.urihttp://creativecommons.org/licenses/by/4.0/deed.no*
dc.subjectFire experimenten_US
dc.subjectCross-laminated timberen_US
dc.subjectExtinguishing systemen_US
dc.subjectLarge-scaleen_US
dc.subjectCompartment fireen_US
dc.subjectEvacuationen_US
dc.subjectSafety way-guidanceen_US
dc.titleLarge-scale fire experiments in a cross-laminated timber compartment with an adjacent corridor – Partly and fully protected with a water sprinkler systemen_US
dc.typePeer revieweden_US
dc.typeJournal articleen_US
dc.description.versionpublishedVersionen_US
dc.rights.holder© 2024 The Authorsen_US
dc.source.volume148en_US
dc.source.journalFire safety journalen_US
dc.identifier.doi10.1016/j.firesaf.2024.104212
dc.identifier.cristin2282767
dc.relation.projectNorges forskningsråd: 294649en_US
dc.source.articlenumber104212en_US
cristin.ispublishedtrue
cristin.fulltextoriginal
cristin.qualitycode2


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record

Navngivelse 4.0 Internasjonal
Except where otherwise noted, this item's license is described as Navngivelse 4.0 Internasjonal