STEM-EDS of Inception Sites of Vented Trees in a HV XLPE Subsea Cable
Hårberg, Sofie Brandtzæg; Nylund, Inger-Emma; Einarsrud, Mari-Ann; Vullum, Per Erik; Lesaint, Cedric Michel; Hvidsten, Sverre
Chapter
Published version
Permanent lenke
https://hdl.handle.net/11250/3120670Utgivelsesdato
2023Metadata
Vis full innførselSamlinger
- Publikasjoner fra CRIStin - SINTEF Energi [1704]
- SINTEF Energi [1836]
Originalversjon
Jicable'23 - 11th International Conference on Power Insulated Cables, Lyon - France 18-22 June 2023 : proceedingsSammendrag
High voltage XLPE cable cores have been subjected to wet ageing following the recommendations in CIGRE TB 722. The electrical ageing was performed at 500 Hz and 10 kV/mm. Vented water trees were detected initiating and growing from the semi-conductive screens. The inception sites of the trees were cut by cryo-microtomy and studied using scanning transmission electron microscopy with energy dispersive X-ray spectroscopy (STEM-EDS). Inorganic impurities were detected on both sides of the smooth XLPE-semiconductive screen interface close to the inception site. KEYWORDS High voltage XLPE cables, Vented water trees, STEM-EDS, Inception site STEM-EDS of Inception Sites of Vented Trees in a HV XLPE Subsea Cable