Impact of AC Outdoor Unit Placement on Energy Efficiency
Chapter, Peer reviewed, Conference object
Published version
Date
2020Metadata
Show full item recordCollections
- SINTEF Proceedings [402]
Abstract
Growing urbanisation in India has led to the increasing development of high-rise buildings. To maintain the building aesthetics, the outdoor air conditioner (AC) units are stacked withing a recessed space. The heat rejected from these outdoor units (ODU) leads to increase in air temperature of the recessed space. This causes inefficient working of AC units. The paper reports the difference in results when on-site measurement data were compared to CFD simulation results. The on-site measurements were taken for six storeys of an eleven-storey building. The different turbulence models were studied, and it was concluded that the NK turbulence model had the least percentage difference of 8.89% when compared to the site data. Further, NK model was used to study the placement of ODUs in recessed spaces having varying depth and width. When the horizontal distance between the ODUs increased by 1m, maximum condenser on-coil temperatures reduced by 6°C. The studies concluded that, even by allocating lesser area to the recessed space, but by optimizing the depth and width of the space, the temperature increase of the microclimate can be avoided and AC efficiency can be maintained.