dc.description.abstractOverheating of metallic ground screen connections at accessories of single core cables are the root cause of severe insulation failures in the distribution network. The overheating is due to a high transition resistance of the connections combined with high induced currents in the ground screens during operation. For copper screened cables equipped with a metallic laminate, overheating causing failures are also observed randomly along the cables often at locations close to cable straps or cleats. Currently there are no international standards with complete tests to determine the ampacity of ground screen connections for different cable system designs making future installations more reliable. Furthermore, product information from the suppliers indicates that basis for design and test criteria is not uniform, and tests are not performed concerning relevant operation and fault scenarios. A research project is launched in Norway, to test different ground screen connections and then to provide guidelines to ensure proper future installations. A new CIRED working group is proposed to provide recommendations for complete tests of ground screen connections lacking in current international standards and brochures.nb_NO
dc.language.isoengnb_NO
dc.relation.ispartof24th International Conference and Exhibition on Electricity Distribution : CIRED 2017 - Proceedings
dc.relation.ispartofseriesCIRED Conference Proceedings;2017
dc.rightsNavngivelse 4.0 Internasjonal*
dc.rights.urihttp://creativecommons.org/licenses/by/4.0/deed.no*
dc.titleExperiences With cable faults located at metallic screen connectionsnb_NO
dc.typeChapternb_NO
dc.typePeer reviewednb_NO
dc.description.versionpublishedVersionnb_NO
dc.rights.holderThe Authorsnb_NO
dc.identifier.cristin1477559
dc.relation.projectNorges forskningsråd: 256261nb_NO
cristin.unitcode7548,30,0,0
cristin.unitnameElkraftteknologi
cristin.ispublishedtrue
cristin.fulltextoriginal
cristin.qualitycode1


Tilhørende fil(er)

Thumbnail

Denne innførselen finnes i følgende samling(er)

Vis enkel innførsel

Navngivelse 4.0 Internasjonal
Med mindre annet er angitt, så er denne innførselen lisensiert som Navngivelse 4.0 Internasjonal