Is Heritage Protection a Limiting Factor for Passive Deep Energy Retrofitting? A Cold-Climate Case Study of University Buildings
Peer reviewed, Journal article
Published version

View/ Open
Date
2025Metadata
Show full item recordCollections
- Publikasjoner fra CRIStin - SINTEF AS [6268]
- SINTEF Community [2412]
Original version
10.3390/heritage8030088Abstract
Reducing the energy consumption of the existing building stock is of paramount importance in the race to reach national and international climate goals. While multiple initiatives are in place and provide guidance, heritage-protected buildings are often not part of the equation. Protected buildings make up a large share of the existing building stock and therefore offer large savings potential. In Trondheim, Norway, alone, that share is close to 10%, which demands the establishment of representative retrofitting cases. A case study of the central buildings on the NTNU campus was established to specifically test passive retrofitting measures, which are greatly affected by heritage protection. The application of measures selected in collaboration with heritage authorities led to overall energy savings of 16% to 18%, while the energy for heating alone was reduced by 34% to 40%. The reductions were especially prominent during cold winter months, where overall consumption peaks were reduced by up to 37%, greatly decreasing the dependence on cold outdoor temperatures. The results make a case for the application of passive retrofitting measures to heritage-protected buildings despite them not reaching deep energy retrofitting goals, especially in cold climates and alongside other energy-saving or -producing measures.