dc.description.abstractDc magnetization due to the geomagnetically induced currents (GICs) and HVDC (High Voltage Direct Current) systems may cause core saturation and result in serious destruction in the transformer performance as well as the power system stability. Based on susceptibility, transformers are classified into different groups. For instance, a three-phase, three-limb transformer is considered less vulnerable to effects of GIC compared to a single-phase or a three-phase, five-limb transformer. However, our study shows that such classifications do not apply to the dc magnetization caused by converter modulation. In this article, we introduce the concept of common mode and differential mode to distinguish dc-bias caused by different mechanisms. Main focus is given on differential mode dc current since it has rarely been reported in any literature. The differential mode dc current was demonstrated by system simulations of classic three-level voltage source converters as well as modular multilevel converter. Detailed experimental investigations were made on a three-phase, three-limb transformer, where the loss impact as well as reactive power consumption were studied. The test shows a significant difference in stray loss between the two modes in three-phase power transformers. Finally, we discuss the effect of delta winding on dc-bias of different modes.en_US
dc.description.abstractCommon and differential mode of dc-bias in three-phase power transformersen_US
dc.language.isoengen_US
dc.publisherSpringeren_US
dc.rightsNavngivelse 4.0 Internasjonal*
dc.rights.urihttp://creativecommons.org/licenses/by/4.0/deed.no*
dc.titleCommon and differential mode of dc-bias in three-phase power transformersen_US
dc.title.alternativeCommon and differential mode of dc-bias in three-phase power transformersen_US
dc.typePeer revieweden_US
dc.typeJournal articleen_US
dc.description.versionpublishedVersionen_US
dc.rights.holderThe Authorsen_US
dc.source.journalElectrical engineering (Berlin. Print)en_US
dc.identifier.doi10.1007/s00202-022-01592-7
dc.identifier.cristin2042183
dc.relation.projectNorges forskningsråd: 255178en_US
cristin.ispublishedtrue
cristin.fulltextoriginal
cristin.qualitycode1


Tilhørende fil(er)

Thumbnail

Denne innførselen finnes i følgende samling(er)

Vis enkel innførsel

Navngivelse 4.0 Internasjonal
Med mindre annet er angitt, så er denne innførselen lisensiert som Navngivelse 4.0 Internasjonal