dc.description.abstractThe aim of this paper is to assess whether reducing the minimum ventilation airflow rate (Vmin) has any negative impacts on perceived air quality (PAQ) upon entering an unoccupied room. Seventeen healthy young adults were asked to assess PAQ in 18 unoccupied classrooms upon entry. Extra pollution sources were introduced in two classrooms, while three other classrooms were not cleaned. The ventilation rate in each classroom was set in a random order to off, low (0.9/1.1 l/s per m2), medium (1.3 l/s per m2) and high (2.0 l/s per m2). Increasing the ventilation rate resulted in a significant improvement of the PAQ-score, with highest PAQ-score when Vmin is set to high and lowest when the ventilation is off. However, most of this increase occurred when increasing ventilation to the low rate. Classrooms that were not cleaned for two days of normal use prior to the test only showed a marked reduced PAQ at all ventilation rates.nb_NO
dc.language.isoengnb_NO
dc.publisherIOP Publishing Ltden
dc.relation.ispartofIAQVECen
dc.rightsCC BY 3.0*
dc.rights.urihttps://creativecommons.org/licenses/by/3.0/*
dc.subjectAir qualityen
dc.subjectVentilationen
dc.subjectEnergy conservationen
dc.subjectHistoric preservationen
dc.subjectindoor air pollutionen
dc.subjectAir-flow-rateen
dc.titleEffect of ventilation on perceived air quality in 18 classroomsnb_NO
dc.typeConference objectnb_NO
dc.typeJournal articlenb_NO
dc.typePeer reviewednb_NO
dc.description.versionpublishedVersionnb_NO
dc.rights.holder© The authorsen
dc.subject.nsiVDP::Teknologi: 500nb_NO
dc.source.pagenumber042038nb_NO
dc.source.volume609nb_NO
dc.source.journalIOP Conference Series: Materials Science and Engineeringnb_NO
dc.identifier.doi10.1088/1757-899X/609/4/042038
dc.identifier.cristin1740080
dc.relation.projectNorges forskningsråd: 255375nb_NO
dc.source.articlenumber042038
cristin.unitcode7401,30,20,0
cristin.unitnameBygninger og installasjoner
cristin.ispublishedtrue
cristin.fulltextoriginal
cristin.qualitycode1


Tilhørende fil(er)

Thumbnail

Denne innførselen finnes i følgende samling(er)

Vis enkel innførsel

CC BY 3.0
Med mindre annet er angitt, så er denne innførselen lisensiert som CC BY 3.0