Neutral Point Overvoltages in Wye-Wye Connected Distribution Transformer Caused by Lightning Current in Low-Voltage Winding
Peer reviewed, Journal article
Accepted version
![Thumbnail](/sintef-xmlui/bitstream/handle/11250/2763806/Gustavsen2020npo_akseptert.pdf.jpg?sequence=5&isAllowed=y)
View/ Open
Date
2020Metadata
Show full item recordCollections
- Publikasjoner fra CRIStin - SINTEF Energi [1632]
- SINTEF Energi [1756]
Original version
10.1109/TPWRD.2020.3027960Abstract
Lightning strokes is a main source of transformer failures in distribution systems. The discharge of a lightning current through a distribution transformer's high-voltage (HV) side arresters leads to a ground potential rise of the transformer tank. In the case of a wye-wye connected transformer with ungrounded HV neutral point, the ground potential rise can drive a current through the low-voltage (LV) side windings that leads to an excessive voltage in the HV side neutral point by inductive transformation. Simulations by a measurement-based model demonstrate that a voltage several times the lightning impulse test voltage can arise in the neutral point, in the case of a close lightning strike to the HV side overhead line. The use of transformer LV side surge arresters in combination with proper grounding on the HV-side are effective ways of reducing the neutral point overvoltage.